Product Profile:
DGG dry-type transformer coil products are arranged inside the axial airway to improve heat dissipation, casting process of science can ensure that the resin fully penetrate into the inter turn and inter layer, between segments to ensure product electrical insulation strength and less partial placed (less than 5pc).
The characteristics of DGG series resin casting thin insulation dry change products made by our company:
1、DGG series dry-type transformer reduces the thickness of the package sealing resin, and enhances the heat dissipation ability of the coil.
2、The coil is strengthened with glass fiber felt, which enhances the mechanical strength of the coil and improves the burst resistance of the product.
3、The coil adopts special technology, greatly reduces the local discharge of coil, improves the coil electrical strength.
4、The low voltage coil adopts foil structure, which reduces the magnetic flux leakage at the end, and improves the ability of products to withstand short circuit burst.
HV winding:
1、Using F insulated copper wire winding glass fiber and epoxy resin composite material as insulation, vacuum pouring
2、The expansion coefficient of glass fiber and epoxy resin composite is similar to that of copper conductor, and it has better impact resistance and crack resistance
3、The pouring resin mixed material can be completely soaked into the coil gap, so that the coil is no bubble, and the coil is placed low
LV winding:
1、The foil conductor in automatic foil winding, internal welding on the winding machine, argon shielded welding, no external welding process
2、F insulation is used between winding layers, and the back end is cured by resin sealing
Performance parameter:
1. 额 定 容 量:30KVA~320KVA
2. Connection group:Iio
3. Noise:<65DB
4.Temperature rise limit:The core is no more than 60K.The core is no more than 60K.
5.Withstand voltage:AC high voltage 6000V 3.5kV / high voltage 10000v 4.2kv/50HZ/5mA/60s without arcing breakdown
6.Operational environment:-10~﹢45℃Relative humidity:Long term work in<90% environment
7. 产品执行标准:GB10229-88,JB9644-1999电气用变压器。
Model implication:
![DGG single-phase high-voltage dry-type transformer: DGG single-phase high-voltage dry-type transformer:]()