Product Profile:
When the AC asynchronous motor starts at rated voltage, the initial starting current is very large.It often exceeds the current of the rated circuit several times (usually 5~7 times).In order to reduce the starting current and not affect the power grid, the method of lowering the voltage is usually used to start the AC asynchronous motor.The product is designed according to the starting characteristics of the high voltage asynchronous motor, matching the motor power 220~1200kw.
Technical characteristics:
The coil is epoxy resin vacuum pouring coil.The epoxy glass grid cloth is strengthened inside and outside the coil, and the F epoxy pouring system is used in the vacuum state.The coil not only has good insulation performance, but also has high mechanical strength, and can withstand large current shock and cold and hot impact without cracking.The end face of the iron core is made of high quality silicon steel sheet end face glue, so that the iron core column and the iron yoke are firmly combined together, and the noise of the product operation is greatly reduced.The advanced vibration and noise reduction structural system includes:(strong clamping of the upper and lower clamps, set torque in strict accordance with the material, the elastic rubber pad is arranged between the clamping piece and a coil, sandwiched between the base and the elastic rubber pad.
Performance parameter:
1. 额定工作电压:6kV/ 10kv 50/60HZ
2.Rated operating current:7A~500A
3.Use altitude:≤2000m
4. Insulation resistance:>100MΩ
5.Reactor noise:<65DB
6.Protection level:IP20
7.Insulation grade:F/H
8.Dielectric strength:32kVAC/50HZ/5mA/60s no arcing breakdown
9.Temperature rise:Iron core≤85K Wire pack temperature≤95K
10.Use environment:-10~45℃, ratings will not reduce the degrees.Up to 55℃.At 45℃ above, the rated current drops by 2% when the temperature is increased by 1℃
11.Product execution standards:GB10229-88, JB9644-1999 semiconductor electric drive reactor
Model implication:
![Starting reactor Starting reactor]()
Starting reactor related parameters:
![Starting reactor Starting reactor]()